Variable Description ATLAUX ATLMDT ATLRPC ATLTFC ATLTGC ATLTRT ATLMMG
has_MixerEnvelope additional mixer module optional (option valid? 1=yes, 0=no) 0 0 0 0 0 0 0
wago_node_nb Number of wago modules 1 2 2 0 2 2 2
Profibus_Monitoring Profibus Monitoring deployed (1=yes, 0=no) 1 1 1 0 1 0 1
CANbus_Monitoring CANbus ELMB status Monitoring deployed (1=yes, 0=no) 0 1 1 0 1 0 1
subdetector System Name AUX MDT RPC TFC TGC TRT MMG
sub_short System Short Name AUX MDT RPC TFC TGC TRT MMG
has_Mixer standard module optional (option valid? 1=yes, 0=no) 0 1 1 0 1 1 1
has_Pump standard module optional (option valid? 1=yes, 0=no) 0 1 1 0 1 1 0
has_Distribution standard module optional (option valid? 1=yes, 0=no) 0 1 1 0 1 1 1
has_PreDistribution standard module optional (option valid? 1=yes, 0=no) 0 0 0 0 0 1 0
has_Purifier standard module optional (option valid? 1=yes, 0=no) 0 0 1 0 1 1 0
has_Absorber standard module optional (option valid? 1=yes, 0=no) 0 0 0 0 0 0 0
has_Exhaust standard module optional (option valid? 1=yes, 0=no) 0 1 1 0 0 1 0
has_Analysis standard module optional (option valid? 1=yes, 0=no) 1 1 1 0 1 1 1
Analysis_chains_count number of Analysis modules 4 1 2 n/a 1 1 2
Analysis_chains_start Option to set first chain number 3 1 1 n/a 1 1 1
has_Humidifier standard module optional (option valid? 1=yes, 0=no) 0 1 1 0 0 0 0
has_Membrane standard module optional (option valid? 1=yes, 0=no) 0 0 0 0 0 1 0
has_Recovery non standard module (valid only in CMS Recovery gas system) 0 0 0 0 0 0 0
has_Liquifier standard module optional (option valid? 1=yes, 0=no) 0 0 0 0 1 0 0
has_IDFlushing non standard module (valid only in ATLAS) 1 0 0 0 0 0 0
has_IDFlushingN2 non standard module (valid only in CMS) 0 0 0 0 0 0 0
has_GasSystem standard module optional in case of AUX there are no gas system option but option will be set to TRUE (to allow profibus HMI generation) (option valid? 1=yes, 0=no) 1 1 1 0 1 1 1
has_Envelops standard module optional (option valid? 1=yes, 0=no) 0 0 0 0 1 1 0
has_Environmental standard module optional (option valid? 1=yes, 0=no) 1 0 0 0 0 0 0
has_Primary standard module optional (option valid? 1=yes, 0=no) 1 0 0 0 0 0 0
has_CF4AbCF4 non standard module (used only in CMS CF4 Recovery gas system) 0 0 0 0 0 0 0
has_CF4AbCO2 non standard module (used only in CMS CF4 Recovery gas system) 0 0 0 0 0 0 0
has_CF4Membrane non standard module (used only in CMS CF4 Recovery gas system) 0 0 0 0 0 0 0
has_CF4Pump non standard module (used only in CMS CF4 Recovery gas system) 0 0 0 0 0 0 0
has_CF4Recovery non standard module (used only in CMS CF4 Recovery gas system) 0 0 0 0 0 0 0
has_GasSystemB non standard module (valid only in ATLAS TFC gas system) 0 0 0 1 0 0 0
has_DistributionB non standard module (valid only in ATLAS TFC gas system) 0 0 0 1 0 0 0
has_PumpB non standard module (valid only in ATLAS TFC gas system) 0 0 0 1 0 0 0
has_Injection non standard module (valid only in ATLAS TFC gas system) 0 0 0 1 0 0 0
has_Circulation non standard module (valid only in ATLAS TFC gas system) 0 0 0 1 0 0 0
has_TROpenSystem TROpen system part of TRT 0 0 0 0 0 1 0
has_XenonDirect valid only in TRT 0 0 0 0 0 1 0
has_SciFiSystem non standard gas system (valid only in LHCb ) 0 0 0 0 0 0 0
dipManagerNumber Dip Manager Number 8 5 3 6 7 4 9
has_AnalysisO2 Analysis O2 FS alarm 0 0 0 0 0 0 0
has_AnalysisH2O Analysis H2O FS alarm 0 0 0 0 0 0 0
has_AnalysisCO2 Analysis CO2 FS alarm 0 0 0 0 0 0 0
has_AnalysisInfraRed Analysis Infrared FS alarm 0 0 0 0 0 0 0
has_XenonRecuperation Purifier Recuperation gas module (only valid for TRD) 0 0 0 0 0 0 0
Analysis_FA_version logic production version 1.0 1.0 1.0 n/a 1.0 n/a 1.0
IDFlushing_FA_version logic production version 1.0 n/a n/a n/a n/a n/a n/a
has_Compressor Gas recuperation Compressor module(option valid? 1=yes, 0=no) 0 0 0 0 0 0 0
has_IDEPAnalysis IDEP Analysis module (option valid? 1=yes, 0=no) 1 0 0 0 0 0 0
IDEPAnalysis_FA_version logic production version 1.0 n/a n/a n/a n/a n/a n/a
has_UTFlushing has_UTFlushing module(option valid? 1=yes, 0=no) 0 0 0 0 0 0 0
GasSystem_Monitoring Soft-FE Gas System Data Analysis 0 1 1 0 1 0 0
Purifier_FA_version Production Purifier logic FA version (=0 not reviewed yet) n/a 1.1 1.1 n/a 1.1 0 1.1
GasSystem_FA_version logic production version n/a 1.0 1.0 n/a 1.0 n/a 1.0
Distribution_FA_version logic production version n/a 1.0 1.0 n/a 1.0 n/a 1.0
Option_BuffPressRegul Buffer pressure regulation (Mixer option)-variable used in Exhaust trends(option valid? 1=yes, 0=No) n/a 0 0 n/a 0 1 0
Mixer_param Mixer parameters used in profibus HMI only(nber of lines) n/a 2 3 n/a 2 3 3
Pump_param Pump parameters used in profibus HMI only(architecture, nber of pump lines) n/a B,2 A,3 n/a A,2 A,2 n/a
Mixer_FA_version logic production version n/a 1.0 1.0 n/a 1.0 1.0 1.0
Distribution_param Distribution parameters used in profibus HMI only(architecture, nber of Groups, option PCVxx26, pnl height) n/a A,1,1,639 A,1,1,639 n/a A,1,1,396 A,1,0,198 A,1,0,198
PumpReg_Option Pressure Regulation handle by the Pump Pressure PT4004 used in Pump and Distribution(0=No regulation from pump, 1= Regulation from Pump) n/a 0 0 n/a 0 0 0
Pump_FA_version logic production version n/a 1.0 1.0 n/a 1.0 1.0 1.0
Purifier_count Number of Purifier modules n/a 1 3 1 1 1 1
Exhaust_param Exhaust parameters used in profibus HMI only(panel height) n/a 198 198 n/a n/a 198 n/a
Exhaust_FA_version logic production version n/a 1.0 1.0 n/a n/a 1.0 1.0
Humidifier_FA_version logic production version n/a 1.0 1.0 n/a n/a n/a 1.0
has_Distr_envelop has Distribution Gas Envelop (1=yes, 0=no) n/a 0 0 0 1 0 0
has_SubDetect_envelop has Sub Detecotor a Gas Envelop (1=yes, 0=no) n/a 0 0 0 0 1 0
SecChambPT 2nd chamber pressure transmitters PTxx04_2 used in Pump and Distribution(option valid? 1=yes, 0=No) n/a 0 0 n/a 0 0 0
Dist_N2Flow Total N2 flow for distribution racks FT6020 (1=FT6020 present, 0=FT6020 Absent) n/a 0 0 n/a 0 0 0
Liquifier_FA_version logic production version n/a n/a n/a n/a 1.0 n/a n/a
Distr_rack61_chls_nb Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 6 n/a n/a
Distr_rack62_chls_nb Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 12 n/a n/a
Distr_rack63_chls_nb Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 6 n/a n/a
Distr_rack64_chls_nb Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 6 n/a n/a
Distr_rack65_chls_nb Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 6 n/a n/a
Distr_rack66_chls_nb Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 12 n/a n/a
Distr_rack67_chls_nb Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 6 n/a n/a
Distr_rack68_chls_nb Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 6 n/a n/a
Distr_rack61_label Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a EM-TGC-L0-C-1 n/a n/a
Distr_rack62_label Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a EI-TGC-L4-C-1 n/a n/a
Distr_rack63_label Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a EM-TGC-L4-C-1 n/a n/a
Distr_rack64_label Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a EM-TGC-L8-C-1 n/a n/a
Distr_rack65_label Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a EM-TGC-L0-A-1 n/a n/a
Distr_rack66_label Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a EM-TGC-L4-A-1 n/a n/a
Distr_rack67_label Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a EI-TGC-L4-A-1 n/a n/a
Distr_rack68_label Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a EM-TGC-L8-A-1 n/a n/a
Option_OutFlow_Distr Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 1 n/a n/a
Option_Interlock_Distr Used only for envelop Dist or Sub HMI generation n/a n/a n/a n/a 1 n/a n/a
XenonRecuperation_FA_version logic production version n/a n/a n/a n/a n/a n/a 1.0