Variable Description ATLAUX
pgssup number of supply chain starting from 1 12
pgsnbr Biggest number of supply chain starting from 10 (add 9) 21
AnaLine Analyse chain (Line nbr) 4
sup10name Primary gas name C2H2F4
sup10FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 1
sup10dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 0
sup10flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup10tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup10netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup10extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup10sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 143
sup10sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 144
sup10WeightVol Volume computation based on bottles weight 1
sup11name Primary gas name SF6
sup11FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 1
sup11dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 0
sup11flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup11tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup11netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup11extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup11sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 145
sup11sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 146
sup11WeightVol Volume computation based on bottles weight 0
sup12name Primary gas name Isobutane
sup12FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 1
sup12dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 0
sup12flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 1
sup12tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 1
sup12netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup12extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup12sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 147
sup12sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 148
sup12WeightVol Volume computation based on bottles weight 1
sup13name Primary gas name Ar_H2
sup13FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 0
sup13dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 0
sup13flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 1
sup13tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup13netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup13extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup13sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 149
sup13sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 150
sup13WeightVol Volume computation based on bottles weight 0
sup14name Primary gas name He
sup14FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 0
sup14dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 0
sup14flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup14tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup14netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup14extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup14sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 151
sup14sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 152
sup14WeightVol Volume computation based on bottles weight 0
sup15name Primary gas name Ar
sup15FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 1
sup15dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 1
sup15flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup15tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup15netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup15extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup15sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 153
sup15sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 154
sup15WeightVol Volume computation based on bottles weight 0
sup16name Primary gas name CO2
sup16FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 1
sup16dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 1
sup16flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup16tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 1
sup16netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 1
sup16extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup16sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 155
sup16sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 156
sup16WeightVol Volume computation based on bottles weight 0
sup17name Primary gas name N2
sup17FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 1
sup17dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 1
sup17flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup17tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup17netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup17extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup17sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 157
sup17sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 158
sup17WeightVol Volume computation based on bottles weight 0
sup18name Primary gas name O2
sup18FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 1
sup18dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 0
sup18flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup18tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup18netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup18extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup18sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 159
sup18sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 160
sup18WeightVol Volume computation based on bottles weight 0
sup19name Primary gas name CF4
sup19FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 0
sup19dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 0
sup19flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup19tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup19netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup19extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup19sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 161
sup19sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 162
sup19WeightVol Volume computation based on bottles weight 0
sup20name Primary gas name Xe
sup20FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 0
sup20dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 0
sup20flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup20tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup20netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup20extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup20sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 163
sup20sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 164
sup20WeightVol Volume computation based on bottles weight 1
sup21name Primary gas name CO2Pur
sup21FlowMeter The gas line has a FlowMeter -is option valid? 1=yes, 0=No 1
sup21dewar Side A is a Dewar: PT1gg19, LT1gg19 -is option valid? 1=yes, 0=No 0
sup21flam Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No 0
sup21tankRTemp Side A/B Reducer Temperature: TT1gg18, TT1gg28 0
sup21netRTemp Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No 0
sup21extra Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No 0
sup21sideAChannel Anayse channel 140+ i connected to the side A -is option valid? 1=yes, 0=No 165
sup21sideBChannel Analyse channel 140+ i connected to the side B -is option valid? 1=yes, 0=No 166
sup21WeightVol Volume computation based on bottles weight 0