| Variable |
Description |
ATLMMG |
ATLRPC |
ATLTRT |
ATLTGC |
ATLMDT |
| wago_node_nb |
Number of wago nodes |
1 |
1 |
1 |
1 |
1 |
| double_mfc |
is double MFC present?(1=Yes 0=No) |
1 |
1 |
1 |
0 |
1 |
| gas_lines |
Number of Mixer gas lines |
3 |
4 |
3 |
2 |
2 |
| Liquid_line |
Number of liquid line |
0 |
0 |
0 |
2 |
0 |
| Double_Liquid_Line |
is liquid line composed of double MFC 1=yes,0=No |
0 |
0 |
0 |
0 |
0 |
| CC_line1 |
Gas name for this CC line1 |
Ar |
C2H2F4 |
Xenon |
CO2 |
Ar |
| CC_line2 |
Gas name for this CC line2 |
CO2 |
i-C4H10 |
CO2 |
n-C5H10 |
CO2 |
| CC_line3 |
Gas name for this CC line3 |
CF4 |
SF6 |
O2 |
n/a |
n/a |
| Option11 |
Liquid level detector LSH1015 (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
1 |
0 |
| Option12 |
Evaporator temperature TE1014 (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
1 |
0 |
| Option13 |
Condenser temperature TE1015 (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
1 |
0 |
| Option14 |
Evaporator pressure PT1014 (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
0 |
0 |
| Option29 |
Heated pipe temperature TE1016 (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
0 |
0 |
| Option50 |
Line i liquid component pump PUMP1i02 (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
1 |
0 |
| Option51 |
Water tank level pressure PT1i10 (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
0 |
0 |
| Option52 |
Water tank level LT1i10 (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
1 |
0 |
| OptionR |
Measured ratio-driven regulation (1= measured ratio by Analysis module, 0= computed by MFC) |
0 |
0 |
1 |
0 |
0 |
| IsFlammable |
Flammable gas interlock XANA9119 (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
0 |
0 |
| Option1 |
External hard-wired interlock ZSH9119 (option valid? 1=yes, 0=No) |
1 |
1 |
1 |
0 |
1 |
| Analysis_chain1_option13 |
Regulation Source Measurements from Analysis module for CO2 -for HMI only (option valid? 1=yes, 0=No) |
0 |
0 |
1 |
0 |
0 |
| Analysis_chain1_option14 |
Regulation Source Measurements from Analysis module for H2O -for HMI only (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
0 |
0 |
| Analysis_chain1_option15 |
Regulation Source Measurements from Analysis module for O2 -for HMI only (option valid? 1=yes, 0=No) |
0 |
0 |
1 |
0 |
0 |
| Analysis_chain1_option16 |
Regulation Source Measurements from Analysis module for IR/Gas -for HMI only (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
0 |
0 |
| Option_BufferLocation |
Exhaust Buffer before detector? buffer pressure acquired by Exhaust (if 1= read by PT5011 if 0 = by PT5005 ) |
0 |
0 |
1 |
0 |
0 |
| Option25 |
Fill pressure regulator PCV1007 (option valid? 1=yes, 0=No) |
0 |
1 |
0 |
0 |
0 |
| Option15 |
Liquid Trap release valve (for TGC, option valid? 1=yes, 0=No) |
0 |
0 |
0 |
1 |
0 |
| Option16 |
External interlock indication from GS -flammable gas detection (for TGC, option valid? 1=yes, 0=No) |
0 |
0 |
0 |
1 |
0 |
| OptionH1 |
Liquid Heater and Temperature (for TGC, option valid? 1=yes, 0=No) |
0 |
0 |
0 |
1 |
0 |
| OptionH2 |
Liquid Heater and Temperature (for TGC, option valid? 1=yes, 0=No) |
0 |
0 |
0 |
1 |
0 |
| test_LEDS |
Pulse to test the Front Panel LEDS (option implemented? 1=yes, 0=No) |
1 |
1 |
1 |
1 |
1 |
| ReInjectionLine |
Reinjection line for recuperated gas (option valid? 1=yes, 0=No) |
0 |
0 |
0 |
0 |
0 |
| CF4Recup |
CF4 Recuperation for ratio computation (option valid? 1=yes, 0=No) |
0 |
n/a |
n/a |
n/a |
n/a |
| CC_line4 |
Gas name for this CC line4 |
n/a |
CO2 |
n/a |
n/a |
n/a |