| Variable |
Description |
ATLAUX |
| pgssup |
number of supply chain starting from 1 |
12 |
| pgsnbr |
Biggest number of supply chain starting from 10 (add 9) |
21 |
| AnaLine |
Analyse chain (Line nbr) |
4 |
| sup10name |
Primary gas name |
C2H2F4 |
| sup10Location |
Primary gas supply 10 location |
3170 SGX1 R-411 |
| sup10Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup10FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
1 |
| sup10dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
0 |
| sup10flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup10tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup10netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup10extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup10sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
143 |
| sup10sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
144 |
| sup10WeightVol |
Volume computation based on bottles weight |
1 |
| sup10PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup11name |
Primary gas name |
SF6 |
| sup11Location |
Primary gas supply 11 location |
3170 SGX1 R-411 |
| sup11Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup11FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
1 |
| sup11dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
0 |
| sup11flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup11tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup11netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup11extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup11sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
145 |
| sup11sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
146 |
| sup11WeightVol |
Volume computation based on bottles weight |
0 |
| sup11PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup12name |
Primary gas name |
Isobutane |
| sup12Location |
Primary gas supply 12 location |
3170 SGX1 R-411 |
| sup12Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup12FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
1 |
| sup12dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
0 |
| sup12flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
1 |
| sup12tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
1 |
| sup12netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup12extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup12sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
147 |
| sup12sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
148 |
| sup12WeightVol |
Volume computation based on bottles weight |
1 |
| sup12PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup13name |
Primary gas name |
Ar_H2 |
| sup13Location |
Primary gas supply 13 location |
3170 SGX1 R-411 |
| sup13Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup13FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
0 |
| sup13dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
0 |
| sup13flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
1 |
| sup13tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup13netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup13extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup13sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
149 |
| sup13sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
150 |
| sup13WeightVol |
Volume computation based on bottles weight |
0 |
| sup13PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup14name |
Primary gas name |
He |
| sup14Location |
Primary gas supply 14 location |
3170 SGX1 R-413 |
| sup14Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup14FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
0 |
| sup14dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
0 |
| sup14flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup14tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup14netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup14extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup14sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
151 |
| sup14sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
152 |
| sup14WeightVol |
Volume computation based on bottles weight |
0 |
| sup14PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup15name |
Primary gas name |
Ar |
| sup15Location |
Primary gas supply 15 location |
3170 SGX1 R-413 |
| sup15Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup15FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
1 |
| sup15dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
1 |
| sup15flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup15tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup15netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup15extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup15sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
153 |
| sup15sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
154 |
| sup15WeightVol |
Volume computation based on bottles weight |
0 |
| sup15PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup16name |
Primary gas name |
CO2 |
| sup16Location |
Primary gas supply 16 location |
3170 SGX1 R-413 |
| sup16Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup16FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
1 |
| sup16dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
1 |
| sup16flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup16tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
1 |
| sup16netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
1 |
| sup16extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup16sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
155 |
| sup16sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
156 |
| sup16WeightVol |
Volume computation based on bottles weight |
0 |
| sup16PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup17name |
Primary gas name |
N2 |
| sup17Location |
Primary gas supply 17 location |
3170 SGX1 R-413 |
| sup17Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup17FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
1 |
| sup17dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
1 |
| sup17flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup17tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup17netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup17extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup17sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
157 |
| sup17sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
158 |
| sup17WeightVol |
Volume computation based on bottles weight |
0 |
| sup17PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup18name |
Primary gas name |
O2 |
| sup18Location |
Primary gas supply 18 location |
3170 SGX1 R-413 |
| sup18Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup18FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
1 |
| sup18dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
0 |
| sup18flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup18tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup18netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup18extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup18sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
159 |
| sup18sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
160 |
| sup18WeightVol |
Volume computation based on bottles weight |
0 |
| sup18PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
0 |
| sup19name |
Primary gas name |
CF4 |
| sup19Location |
Primary gas supply 19 location |
3170 SGX1 R-413 |
| sup19Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup19FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
0 |
| sup19dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
0 |
| sup19flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup19tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup19netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup19extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup19sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
161 |
| sup19sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
162 |
| sup19WeightVol |
Volume computation based on bottles weight |
0 |
| sup19PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup20name |
Primary gas name |
Xe |
| sup20Location |
Primary gas supply 20 location |
3170 SGX1 R-413 |
| sup20Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup20FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
0 |
| sup20dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
0 |
| sup20flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup20tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup20netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup20extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup20sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
163 |
| sup20sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
164 |
| sup20WeightVol |
Volume computation based on bottles weight |
1 |
| sup20PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| sup21name |
Primary gas name |
CO2Pur |
| sup21Location |
Primary gas supply 21 location |
3170 SGX1 R-413 |
| sup21Exist |
Supply is present -is option valid? 1=yes, 0=No |
1 |
| sup21FlowMeter |
The gas line has a FlowMeter -is option valid? 1=yes, 0=No |
1 |
| sup21dewar |
Side A is a Dewar: PT1gg19, LT1gg19 (0= none, 1= LTxx and PTxx, 2=LTxx only) |
0 |
| sup21flam |
Gas is flammable: PSL1gg04-is option valid? 1=yes, 0=No |
0 |
| sup21tankRTemp |
Side A/B Reducer Temperature: TT1gg18, TT1gg28 |
0 |
| sup21netRTemp |
Network pressure reducer temperature: TT1gg08 -is option valid? 1=yes, 0=No |
0 |
| sup21extra |
Batteries Pressure Reducer Temperature (maybe): TT1gg05 -is option valid? 1=yes, 0=No |
0 |
| sup21sideAChannel |
Anayse channel 140+ i connected to the side A (0=not connected to Analysis) |
165 |
| sup21sideBChannel |
Analyse channel 140+ i connected to the side B (0=not connected to Analysis) |
166 |
| sup21WeightVol |
Volume computation based on bottles weight |
0 |
| sup21PSH1222 |
High Pressure Switch PSHgg12 and PSHgg22 -is option valid? 1=yes, 0=No |
1 |
| test_LEDS |
Pulse to test the Front Panel LEDS (option implemented? 1=yes, 0=No) |
1 |
| wago_node_nb |
|
3 |