Variable |
Description |
LHBAUX |
LHBMWP |
LHBRI1 |
LHBRI2 |
Analysis_FA_version |
logic production version |
1.0 |
n/a |
n/a |
1.0 |
has_MixerEnvelope |
additional mixer module optional (option valid? 1=yes, 0=no) |
0 |
0 |
0 |
0 |
wago_node_nb |
Number of wago modules |
1 |
2 |
2 |
2 |
subdetector |
System Name |
AUX |
MWP |
RI1 |
RI2 |
sub_short |
System Short Name |
AUX |
MWP |
RI1 |
RI2 |
has_Mixer |
standard module optional (option valid? 1=yes, 0=no) |
0 |
1 |
1 |
1 |
has_Pump |
standard module optional (option valid? 1=yes, 0=no) |
0 |
1 |
1 |
1 |
has_Distribution |
standard module optional (option valid? 1=yes, 0=no) |
0 |
1 |
1 |
1 |
has_PreDistribution |
standard module optional (option valid? 1=yes, 0=no) |
0 |
0 |
0 |
0 |
has_Purifier |
standard module optional (option valid? 1=yes, 0=no) |
0 |
1 |
1 |
1 |
has_Absorber |
standard module optional (option valid? 1=yes, 0=no) |
0 |
0 |
0 |
0 |
has_Exhaust |
standard module optional (option valid? 1=yes, 0=no) |
0 |
1 |
1 |
1 |
has_Analysis |
standard module optional (option valid? 1=yes, 0=no) |
1 |
0 |
0 |
1 |
chains_count |
Number of Analysis modules |
2 |
n/a |
n/a |
1 |
has_Humidifier |
standard module optional (option valid? 1=yes, 0=no) |
0 |
0 |
0 |
0 |
has_Membrane |
standard module optional (option valid? 1=yes, 0=no) |
0 |
0 |
1 |
1 |
has_Recovery |
non standard module (valid only in CMS Recovery gas system) |
0 |
0 |
0 |
0 |
has_Liquifier |
standard module optional (option valid? 1=yes, 0=no) |
0 |
0 |
1 |
0 |
has_IDFlushing |
non standard module (valid only in ATLAS) |
0 |
0 |
0 |
0 |
has_IDFlushingN2 |
non standard module (valid only in CMS) |
0 |
0 |
0 |
0 |
has_GasSystem |
standard module optional (option valid? 1=yes, 0=no) |
0 |
1 |
1 |
1 |
has_Envelops |
standard module optional (option valid? 1=yes, 0=no) |
0 |
0 |
0 |
0 |
has_Environmental |
standard module optional (option valid? 1=yes, 0=no) |
1 |
0 |
0 |
0 |
has_Primary |
standard module optional (option valid? 1=yes, 0=no) |
1 |
0 |
0 |
0 |
has_CF4AbCF4 |
non standard module (used only in CMS CF4 Recovery gas system) |
0 |
0 |
0 |
0 |
has_CF4AbCO2 |
non standard module (used only in CMS CF4 Recovery gas system) |
0 |
0 |
0 |
0 |
has_CF4Membrane |
non standard module (used only in CMS CF4 Recovery gas system) |
0 |
0 |
0 |
0 |
has_CF4Pump |
non standard module (used only in CMS CF4 Recovery gas system) |
0 |
0 |
0 |
0 |
has_CF4Recovery |
non standard module (used only in CMS CF4 Recovery gas system) |
0 |
0 |
0 |
0 |
has_GasSystemB |
non standard module (valid only in ATLAS TFC gas system) |
0 |
0 |
0 |
0 |
has_DistributionB |
non standard module (valid only in ATLAS TFC gas system) |
0 |
0 |
0 |
0 |
has_PumpB |
non standard module (valid only in ATLAS TFC gas system) |
0 |
0 |
0 |
0 |
has_Injection |
non standard module (valid only in ATLAS TFC gas system) |
0 |
0 |
0 |
0 |
has_Circulation |
non standard module (valid only in ATLAS TFC gas system) |
0 |
0 |
0 |
0 |
has_TROpenSystem |
non standard module (valid only for TROpen system part of TRT) |
0 |
0 |
0 |
0 |
has_XenonDirect |
non standard module (valid only for TROpen system part of TRT) |
0 |
0 |
0 |
0 |
dipManagerNumber |
Dip Manager Number |
1 |
1 |
1 |
1 |
has_AnalysisO2 |
Analysis O2 FS alarm (option valid? 1=yes, 0=no) |
0 |
0 |
0 |
0 |
has_AnalysisH2O |
Analysis H2O FS alarm (option valid? 1=yes, 0=no) |
0 |
0 |
0 |
0 |
has_AnalysisCO2 |
Analysis CO2 FS alarm (option valid? 1=yes, 0=no) |
0 |
0 |
0 |
0 |
has_AnalysisInfraRed |
Analysis Infrared FS alarm (option valid? 1=yes, 0=no) |
0 |
0 |
0 |
0 |
SecChambPT |
2nd chamber pressure transmitters PTxx04_2 used in Pump and Distribution(option valid? 1=yes, 0=No) |
0 |
0 |
1 |
1 |
has_XenonRecuperation |
Purifier Recuperation gas module (only valid for TRD) |
0 |
0 |
0 |
0 |
XenonRecuperation_FA_version |
logic production version |
1.0 |
1.0 |
1.0 |
1.0 |
has_SciFiSystem |
non standard gas system (valid only in LHCb ) |
0 |
0 |
0 |
0 |
has_Compressor |
Gas recuperation Compressor module(option valid? 1=yes, 0=no) |
0 |
0 |
0 |
1 |
Option_BuffPressRegul |
Buffer pressure regulation (Mixer option)-variable used in Exhaust trends(option valid? 1=yes, 0=No) |
n/a |
0 |
1 |
1 |
Mixer_param |
Mixer parameters used in profibus HMI only(nber of lines) |
n/a |
3 |
1 |
2 |
Pump_param |
Pump parameters used in profibus HMI only(architecture, nber of pump lines) |
n/a |
B,2 |
A,2 |
A,2 |
Distribution_param |
Distribution parameters used in profibus HMI only(architecture, nber of Groups,option PCVxx26, pnl height) |
n/a |
B,3,0,198 |
A,1,0,198 |
A,1,0,198 |
Purifier_count |
number of Purifier modules |
n/a |
1 |
1 |
1 |
Exhaust_param |
Exhaust parameters used in profibus HMI only(panel height) |
n/a |
198 |
198 |
198 |
has_Distr_envelop |
Gas Envelop module type optional (option valid? 1=yes, 0=no) |
n/a |
0 |
0 |
0 |
has_SubDetect_envelop |
Gas Envelop module type optional (option valid? 1=yes, 0=no) |
n/a |
0 |
0 |
0 |
GasSystem_FA_version |
Production GasSystem logic FA version (=0 not reviewed yet) |
n/a |
1.0 |
n/a |
1.0 |
PumpReg_Option |
Distribution Pressure Regulation handle by the Pump Pressure PT4004 (0=No regulation from pump, 1= Regulation from Pump) |
n/a |
0 |
0 |
1 |
Dist_N2Flow |
Total N2 flow for distribution racks FT6020 (1=FT6020 present, 0=FT6020 Absent) |
n/a |
0 |
0 |
0 |
Purifier_FA_version |
Production Purifier logic FA version (=0 not reviewed yet) |
n/a |
1.1 |
0 |
1.1 |
Mixer_FA_version |
Production Mixer logic FA version (=0 not reviewed yet) |
n/a |
1.0 |
1.0 |
1.0 |
Pump_FA_version |
Production Pump logic FA version (=0 not reviewed yet) |
n/a |
1.0 |
1.0 |
1.0 |
Exhaust_FA_version |
Production Exhaust logic FA version (=0 not reviewed yet) |
n/a |
1.0 |
1.0 |
1.0 |
Distribution_FA_version |
Production Distribution logic FA version (=0 not reviewed yet) |
n/a |
1.0 |
n/a |
1.0 |
Liquifier_FA_version |
Production Liquifier logic FA version (=0 not reviewed yet) |
n/a |
n/a |
1.0 |
n/a |
Compressor_FA_version |
Compressor logic FA version (=0 not reviewed yet) |
n/a |
n/a |
n/a |
1.0 |